Products Details
Technical Data - Pole No.: 1, 1P+N, 2, 3, 3P+N, 4
- Rated voltage: AC 230/400V
- Rated current (A):1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63A
- Tripping curve: B, C, D
- High short-circuit breaking capacity (Icn): 10kA
- Rated service short-circuit breaking capacity(Ics): 7.5kA
- Rated frequency: 50/60Hz
- Energy limiting class: 3
- Rated impulse withstand voltage: 6.2kV
- Electro-mechanical endurance: 20000
- Contact position indication
- Connection terminal:Screw terminal/Pillar terminal with clamp
- Connection capacity: Rigid conductor up to 25mm²
- Terminal Connection Height: 19mm
- Fastening torque: 2.0Nm
- Installation:On symmetrical DIN rail 35mm/Panel mounting
Power Conumption
Rated Current Range (InA) | Max consumption/pole (W) |
In≤10 | 3 |
10<In≤16 | 3.5 |
16<In≤25 | 4.5 |
25<In≤32 | 6 |
32<In≤40 | 7.5 |
40<In≤50 | 9 |
50<In≤63 | 13 |
Overload Current Protection Characteristics
Test Current | Type | Test procedure | Initial State | Tripping or Non-tripping Time Limit | Expected Result | Remark |
A | B,C,D | 1.13In | cold | t≤1h | no tripping | |
B | B,C,D | 1.45In | after test a | t<1h | tripping | Current in the 5s in th increase of stability |
C | B,C,D | 2.55In | cold | 1s<t<60s(In≤32A)/1s<t<120s(n>32A) | tripping | |
D | B | 3In | cold | t≥0.1s | no tripping | Turn on the auxiliary switch to |
C | 5In | |
D | 10In | |
E | B | 5In | | t<0.1s | tripping | Turn on the auxiliary switch to |
C | 10In | cold |
D | 20In | |