Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40

CJRO2-40 Residual Current circuit breaker with overload protection (RCBO) ensure electrical safety in homes and similar situations, such as offices and other buildings as well as for industrial applications by protecting electrical installations against leakage Current reach to 30mA and against overloads and short circuits. Once a fault is detected, the RCBO automatically switches off the electrical circuit to prevent risk to the people and prevent damage to wires and to avoid the risk of fire. Warranting reliability and safety for people and assets, RCBO are equipped with AC,A type. The AC type is a common type use for homes, A type with pulse DC protection, normally the rated current is 6,10,16,20,25,32A,leakage current protection is 30mA,100mA,300mA and rated voltage is 230VAC. frequency is 50/60Hz. according to IEC61009-1/EN61009-1 standards.

Products Details

Construction and Feature

  • Provides protection against earth fault/leakage current, short-circuit, overload, and function of isolation.
  • Contact position indication
  • Provides protection against indirect contact by human body
  • Provides complementary protection against direct contact by human body.
  • Effectively protects electric equipment against insulating failure
  • Equipped with switched neutral and phase pole
  • Provides protection against over-voltage
  • Provides comprehensive protection to household and commercial distribution systems.
  • S2 Shunt Tripper
  • U2+O2 Over-voltage and under-voltage tripper
 

Technical Data

Standard IEC61009-1/EN61009-1
Type Electronic type
Residual current characteristics AC
Pole No 1P+N
Tripping curve B, C, D
Rated short-circuit capacity 6kA
Rated current (A) 6A, 10A, 16A, 20A, 25A, 32A
Rated voltage 230V AC
Rated frequency 50/60Hz
Rated residual operating current(mA) 0.03, 0.1, 0.3
Tripping duration instantaneous≤0.1s
Electro-mechanical endurance 4000 cycles
Connection terminal pillar terminal with clamp
Terminal Connection Height H1=16mm  H2=21mm
Over-voltage tripping 280V±5%
Connection capacity Flexible conductor 10mm²
Rigid conductor 16mm²
Installation On symmetrical DIN rail 35.5mm
Panel mounting
 

Overload Current Protection Characteristics

Test procedure Type Test Current Initial State Tripping or Non-tripping Time Limit Expected Result Remark
a B,C,D 1.13In cold t≥1h no tripping
b B,C,D 1.45In after test a t<1h tripping Current in the 5s in th increase of stability
c B,C,D 2.55In cold 1s<t<60s tripping
d B 3In cold t≤0.1s no tripping Turn on the auxiliary switch to close the current
C 5In
D 10In
e B 5In cold t<0.1s tripping Turn on the auxiliary switch to close the current
C 10In
D 20In
The terminology  “cold state” refes to that no load is carried before testing at the reference setting temperature.
 

Residual Current Action Breaking Time

Residual Current Action Breaking Time
type In/A I△n/A Residual Current (I△) Is Corresponding To The Following Breaking Time (S)
I△n 2 I△n 5 I△n 5A,10A,20A,50A,100A,200A,500A I△t
general type any value any value 0.3 0.15 0.04 0.04 0.04 Max Break-time
 

A Type Of Trip Current Range

Lagangle(A) A Tripping Current(A)
Lower Limit Upper Limit
0.35 I△n 0.14 I△n
90° 0.25 I△n
135° 0.11 I△n