Standard | IEC/BS/EN62606,IEC/AS/NZS 61009.1 (RCBO) |
Rated current | 6,10,13,16,20,25,32,40A |
Rated voltage | 230/240V AC |
Rated frequency | 50/60Hz |
Maximum operating voltage | 1.1Un |
Minimum operating voltage | 180V |
Protection degree | IP20 /IP40 (Terminals/Housing) |
Type & mounting arrangement | Din-Rail |
Application | Consumer unit |
Tripping curve | B,C |
Rated residual making and breaking capacity (I△m) | 2000A |
Mechanical operations | >10000 |
Electrical operations | ≥1200 |
Rated residual operating current (I△n) | 10,30,100,300mA |
Rated short-circuit capacity (Icn) | 6kA |
AFDD Test means | Automatic test function as per 8.17 IEC 62606 |
Classification as per IEC 62606 | 4.1.2 - AFDD unit integrated in a protective device |
Ambient operating temperature | -25°C to 40°C |
AFDD ready indication | Single LED Indication |
Overvoltage function | Overvoltage condition of 270Vrms to 300Vrms for 10 seconds will cause device to trip.LED indication of over-voltage trip will be provided on product re-latch. |
Self test interval | 1 Hour |
Earth fault current | Trip time limit (typical measured value) |
0.5 x Idn | No trip |
1 x Idn | <300 ms (nominally <40 ms) |
5 x Idn | <40ms (nominally <40 ms)Actual Tripping Threshold |