Arc Fault Detection Device(AFDD) CJAF1

CJAF1 Single module AFDD/RCBO with switched N pole provides the highest levels of protection for the installation and its users. It combines the function of a residual current operated device for earth leakage detection, overcurrent protection for short-circuit and Arc fault detection for both parallel and series arcs. The device is intended to reduce the risk of fires by ignition from electrical sources. Because of one module width, it does not require larger consumer units and AFDD can easily be retro fitted into existing installations.

Products Details

Specification

Standard IEC/BS/EN62606,IEC/AS/NZS 61009.1 (RCBO)
Rated current 6,10,13,16,20,25,32,40A
Rated voltage 230/240V AC
Rated frequency 50/60Hz
Maximum operating voltage 1.1Un
Minimum operating voltage 180V
Protection degree IP20 /IP40 (Terminals/Housing)
Type & mounting arrangement Din-Rail
Application Consumer unit
Tripping curve B,C
Rated residual making and breaking capacity (I△m) 2000A
Mechanical operations >10000
Electrical operations ≥1200
Rated residual operating current (I△n) 10,30,100,300mA
Rated short-circuit capacity (Icn) 6kA
AFDD Test means Automatic test function as per 8.17 IEC 62606
Classification as per IEC 62606 4.1.2 - AFDD unit integrated in a protective device
Ambient operating temperature -25°C to 40°C
AFDD ready indication Single LED Indication
Overvoltage function Overvoltage condition of 270Vrms to 300Vrms for 10 seconds will cause device to trip.LED indication of over-voltage trip will be provided on product re-latch.
Self test interval 1 Hour
Earth fault current Trip time limit (typical measured value)
0.5 x Idn No trip
1 x Idn <300 ms (nominally <40 ms)
5 x Idn <40ms (nominally <40 ms)Actual Tripping Threshold

Operation and Display

■LED Indication: □After tripping under a fault condition the fault status indicator will show the fault nature according to the table opposite. □LED flashing sequence repeats every 1.5sec for next 10 sec after powering up ■Series Arc Fault: □1 Flash - Pause - 1 Flash - Pause - 1 Flash ■Parallel Arc Fault: □1 2 Flashes - Pause - 2 Flashes - Pause - 2 Flashes ■Over Voltage Fault: □3 Flashes - Pause - 3 Flashes - Pause - 3 Flashes ■Self-Test Fault: □1 Flash - Pause -1 Flash - Pause -1 Flash (At Double Rate) product-description1