| Standard | IEC61008 |
| Mode | Electro-magnetic type, electronic type |
| Residual current characteristics | A, AC |
| Pole No | 2P, 4P |
| Rated making and breaking capacity | 500A(In=25A,40A) or 10InA(In=63A,80A,100A,125A) |
| Rated current(A) | 25, 40, 63 |
| Rated voltage | AC 230(240)/400(415) |
| Rated frequency | 50/60Hz |
| Rated residual operating current I△n(A) | 0.03, 0.1, 0.3, 0.5 |
| Rated residual non operating current I△no | 0.5I△n |
| Rated conditional short-circuit current Inc | 10kA |
| Rated conditional residual short-circuit Current I△c | 10kA |
| Tripping duration | instantaneous tripping ≤0.3s(0.1) |
| Residual tripping current range | 0.5I△n~I△n |
| Electro-mechanical endurance | 4000 cycles |
| Connection capacity | Rigid conductor 25mm² |
| Terminal Connection Height | 21mm |
| Connection terminal | Pillar terminal with clamp |
| Fastening torque | 2.0Nm |
| Installation | On symmetrical DIN rail 35.5mm |
| Panel mounting |
| Protection class | IP20 |